Estimated Lead Time : 4 - 6 weeks.
Manufacturer : Schneider Electric
Analog input module - 2I - Thermocouple J/K/N/S - 16 bits
Range of product :Modicon TM5
Product or component type :Analog input module
Analogue input number :2
Analogue input type :Thermocouple - 210...1200 °C with thermocouple J | thermocouple - 270...1300 °C with thermocouple N | thermocouple - 270...1372 °C with thermocouple K | thermocouple - 50...1768 °C with thermocouple S
Analogue input resolution :16 bits
Complementary
Range compatibility :Modicon M258 | Modicon LMC058
Product compatibility :Logic controller | Motion controller
Measurement resolution :0.1 °C
Colour :White
Input filtering :1...66.7 ms configurable by software
Measurement error :+/- 0.1 % of full scale - 210...1200 °C thermocouple J at 25 °C | +/- 0.11 % of full scale - 270...1300 °C thermocouple N at 25 °C | +/- 0.11 % of full scale - 270...1372 °C thermocouple K at 25 °C | +/- 0.17 % of full scale - 50...1768 °C thermocouple S at 25 °C
Temperature coefficient :0.01 %FS/°C, analogue input type: thermocouple
Non-linearity :+/- 0.001 %FS, analogue input type: thermocouple
Type of cable :Shielded cable
Isolation :No insulation between channels | 500 Vrms AC insulation between channel and bus
Supply :Internal
[Us] rated supply voltage :24 V DC -15...20 %
Common mode rejection :> 70 dB
Local signalling :1 LED green for power supply | 1 LED red for power supply | 2 LEDs green for input status
Current consumption :2 mA at 5 V DC bus | 30 mA at 24 V DC input/output
Maximum power dissipation in W :0.73 W
Marking :CE
Product weight :0.025 kg
Environment
Standards :UL 508 | CSA C22.2 No 142 | CSA C22.2 No 213 | IEC 61131-2
Product certifications :CSA | GOST-R | C-Tick | cULus
Ambient air temperature for operation :0…55 °C without derating (horizontal installation) | 0…60 °C with derating factor (horizontal installation) | 0…50 °C (vertical installation)
Ambient air temperature for storage :-25…70 °C
Relative humidity :5…95 % without condensation
IP degree of protection :IP20 conforming to IEC 61131-2
Pollution degree :2 conforming to IEC 60664
Operating altitude :0...2000 m
Storage altitude :0…3000 m
Vibration resistance :1 gn at 8.4…150 Hz on DIN rail | 3.5 mm at 5…8.4 Hz on DIN rail
Shock resistance :15 gn for 11 ms
Resistance to electrostatic discharge :4 kV on contact conforming to EN/IEC 61000-4-2 | 8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields :1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3 | 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Resistance to fast transients :1 kV (I/O) conforming to EN/IEC 61000-4-4 | 1 kV (shielded cable) conforming to EN/IEC 61000-4-4 | 2 kV (power lines) conforming to EN/IEC 61000-4-4
Surge withstand :0.5 kV differential mode conforming to EN/IEC 61000-4-5 | 1 kV common mode conforming to EN/IEC 61000-4-5
Electromagnetic compatibility :EN/IEC 61000-4-6
Disturbance radiated/conducted :CISPR 11
Packing Units
Unit Type of Package 1 :PCE
Number of Units in Package 1 :1
Package 1 Height :2.000 cm
Package 1 Width :6.000 cm
Package 1 Length :10.500 cm
Package 1 Weight :41.000 g
Unit Type of Package 2 :S02
Number of Units in Package 2 :97
Package 2 Height :15.000 cm
Package 2 Width :30.000 cm
Package 2 Length :40.000 cm
Package 2 Weight :4.263 kg
Shipping weight : 1 Kg