MTL4516 | MTL Instruments | Switch / Proximity Detector Interface (Stop Production. New Replacement : MTL4516C Switch / Proximity Detector Interface)
MTL4516 | MTL Instruments | Switch / Proximity Detector Interface (Stop Production. New Replacement : MTL4516C Switch / Proximity Detector Interface)

MTL4516 | MTL Instruments | Switch / Proximity Detector Interface (Stop Production. New Replacement : MTL4516C Switch / Proximity Detector Interface)

0 Review(s)
USD126.00
Retail Price:USD145.00
Your Savings:USD19.00(13%)
Availability:
Part Number: MTL4516
Manufacturer:MTL Instruments
Condition : Brand New
Warranty : 12 monthsĀ 
Write a Review

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com.All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

NII REF No : IA111311041120

  • This product has been replaced with MTL4516C Switch/ Proximity Detector Interface

  • Manufacturer : MTL Instruments

  • Product No. : MTL4516

  • Product Type : Switch / Proximity Detector Interface

  • Number of channels : Two

  • Location of switches

    Zone 0, IIC, T6 hazardous area

    Div. 1, Group A hazardous location

  • Location of proximity detector

    Zone 0, IIC, T4–6 hazardous area if suitably certified

    Div. 1, Group A hazardous location

  • Hazardous-area inputs

    Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)

  • Voltage applied to sensor : 7 to 9V dc from 1k? ±10%

  • Input/output characteristics

    • Normal phase

      Outputs closed if input > 2.1mA (< 2k? in input circuit)

      Outputs open if input < 1.2mA (> 10k? in input circuit)

    • Hysteresis : 200µA (650?) nomina

  • Line fault detection (LFD) (when selected)

    User-selectable via switches on the side of the unit. Line faults are indicated by an LED for each channel. The channel output relay is de-energised if an input line fault is detected.

    Open-circuit alarm on if Iin < 50µA

    Open-circuit alarm off if Iin > 250µA

    Short-circuit alarm on if Rin < 100?

    Short-circuit alarm off if Rin > 360?

  • Safe-area output : Two single-pole relays with changeover contacts

  • Maximum current consumption : 35mA at 24V

  • Power dissipation within unit : 0.84W at 24V

  • LED indicators

    Green: power indication

    Yellow: two: channel status, on when output energised

    Red: two: LFD indication, on when line fault detected

  • Safety description (each channel) : Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc

  • Dimensions ( D x W x H ) : 1.58 cm x 10.98 cm x 12.36 cm

  • Weight : Approx. 0.11 Kg

  • Shipping Weight : 1.5 Kg