Product No.: FX3U-ENET-ADP
Product type: Ethernet Interface Block
Transmission Specifications Data transmission speed: 100Mbps or 10Mbps,
Communication mode: Full / half duplex
Transmission method: Baseband
The maximum segment length: 100m
The maximum number of nodes / connection: 10BASE-T: cascade up to four stages
100BASE-TX: cascade up to two-stage
above is the connection possible number of stages at the time of use repeater hub.
Can be connected to the number of stages at the time of switching hub used, please check with the manufacturer of the switching hub to be used.
Connector: RJ45
Number of connections: MELSOFT connection + MC protocol + data monitoring ? 4 connection
It can be connected to the number of the basic unit: One
Ethernet adapter, as well as the communication function expansion board and other communication special adapter, and 1 channel the communication channel (CH) occupation.
Apply PLC: FX3S, FX3G (V2.00 or later), FX3U (since V3.10), FX3GC (V2.00 or later), FX3UC (V3.10 or later)
connection to the FX3S is required FX3S-CNV-ADP.
Connection to the FX3G is required FX3G-CNV-ADP.
FX3U, connection to the FX3UC-32MT-LT (-2), you must have the function expansion board.
Power Specifications:
Power supply: 30mA / DC5V (internal power supply from DC5V power of the basic unit)
Allowable momentary power failure time: As well as the sequencer to be connected
Ambient temperature: 0 ~ 55 °C ····· operation, -25 ~ 75 °C ····· during storage
Relative humidity: 5 ~ 95% RH (non-condensing) ...... operation
Vibration resistance When the DIN rail mounting Frequency: 10 ~ 57Hz: Half amplitude: 0.035mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
Frequency: 57 ~ 150Hz: Acceleration: 4.9m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
Direct mounting at the time Frequency: 10 ~ 57Hz: Half amplitude: 0.075mm X, Y, Z each direction 10 times (for a total of each 80 minutes)
Frequency: 57 ~ 150Hz: Acceleration: 9.8m / s2 X, Y, Z each direction 10 times (for a total of each 80 minutes)
Impact resistance: 147m / s2, duration of action 11ms, X at half-sine pulse, Y, Z directions 3 times each
Anti-noise: Noise voltage 1,000Vp-p, noise width 1µs, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator
Withstand voltage: All terminals and between the ground terminal: AC500V 1 minute
Insulation resistance: All terminals and between the ground terminal: DC500V 5MO more in insulation resistance tester
Working environment: Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly
Use advanced: 2000m or less
can not be used in the pressurized environment to more than atmospheric pressure. There is a possibility of failure.
- Weight : 0.1 Kg