RM7896A1012/U | Honeywell | 120V, 50/60 HZ. 15 SEC POSTPURGE.

RM7896A1012/U | Honeywell | 120V, 50/60 HZ. 15 SEC POSTPURGE.

Your Price: $571.00
Retail Price:$700.00
Your Savings:$129.00(18%)
Estimated Lead Time : 6 Weeks
Part Number:RM7896A1012/u
  • Minimum Order Quantity (MOQ):1

Condition : Brand New

Warranty : 12 months 

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

  • Estimated Lead Time: 6 - 8 Weeks.

  • RM7896A1012/U

  • On-Off Primary Control with Pre- and Post-Purge-Intermittent Pilot

  • Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.

  • Subbase, amplifier and purge card are required for operation.

  • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and

  • COMBUSTION SYSTEM MANAGER™ software.

  • 15 second postpurge.

  • Five LEDs provide sequence information.

  • Interchangeable plug-in flame amplifiers.

  • Local or remote annunciation of operation and fault information.

  • Nonvolatile memory retains history files and sequencing status after power loss.

  • Optional remote reset capability.

  • Optional report generation.

  • Selectable recycle or lockout on loss of airflow or flame.

  • Shutter drive output.

  • Airflow switch check.

  • Delayed main valve

  • Application : On-Off Primary Control with Pre and Post purge

  • Dimensions (in.) :5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase

  • Dimensions (mm) :127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase

  • Weight (lb) :1 lb 15 oz

  • Weight (kg) :0.9 kg

  • Comments :Includes Pre- and Post -Purge.

  • Frequency :50 Hz; 60 Hz (±10%)

  • Approvals, Underwriters Laboratories Inc. :Component Recognized, File No. MP268; Guide No. MCCZ.

  • Approvals, CSA :Certified, File No. LR95329-3.

  • Voltage :120 Vac (+10, -15%)

  • Shipping and Storage Temperature Range (F) :-40 F to +140 F

  • Shipping and Storage Temperature Range (C) :-40 C to +60 C

  • Approvals, Federal Communications Commission :FCC Part 15, Class B, Emissions.

  • Flame Establishing Period - Pilot :4 sec or 10 sec

  • Flame Establishing Period - Main :Intermittent

  • Interlocks :Selectable

  • PrePurge :Determined by ST7800A Purge Timer Card

  • PostPurge :15 sec

  • Required Components :Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-

  • in Purge Timer Card.

  • Delayed Main Valve :No

  • Pilot Type :intermittent

  • Vibration :0.5 G environment

  • Approvals, Swiss RE :Acceptable

  • Approvals, Factory Mutual :Report No. OX4A5.AF.

  • Shipping Weight: 2 Kg