R7140L1009/U | Honeywell | R7140G,L,M Burner Control Modules (Discontinued With No Replacement)
R7140L1009/U | Honeywell | R7140G,L,M Burner Control Modules (Discontinued With No Replacement)

R7140L1009/U | Honeywell | R7140G,L,M Burner Control Modules (Discontinued With No Replacement)

0 Review(s)
USD791.00
Retail Price:USD909.00
Your Savings:USD118.00(13%)
Availability: Estimated Lead Time : 8 - 10 weeks.
Part Number: R7140L1009/u
Manufacturer:Honeywell
Condition : Brand New
Warranty : 12 monthsĀ 
  • Minimum Order Quantity (MOQ): 1
Write a Review

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com.All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

NII REF No : IAFD111811041126

  • Discontinued With No Replacement

  • Manufacturer: Honeywell

  • 120V, 50/60 HZ.

  • R7140L1009/U

  • Upgrade Replacement Programming Control

  • The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications.

  • Functions provided by the R7140G,L,M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.

  • Upgrade replacement for BC7000 or R4140 legacy Programmer controls.

  • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.

  • Application:Upgrade Replacement Programming Control for R4140 or BC7000

  • Dimensions (in.):7 in. wide x 6 5/32 high x 5 3/4 in. deep

  • Dimensions (mm):177 mm wide x 156 mm high x 146 mm deep

  • Weight (lb):3 lb 1 oz

  • Weight (kg):1.4 kg

  • Comments: LHL-LF&HF Proven

  • Frequency: 50 Hz; 60 Hz (±10%)

  • Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ.

  • Voltage: 120 Vac (+10, -15%)

  • Shipping and Storage Temperature Range (F): -40 F to +140 F

  • Shipping and Storage Temperature Range (C): -40 C to +60 C

  • Approvals, Federal Communications Commission: FCC Part 15, Class B, Emissions.

  • Flame Establishing Period - Pilot: 4 sec or 10 sec

  • Flame Establishing Period - Main: 10 sec or 15 sec

  • Interlocks: Lockout

  • Preignition: Yes

  • PrePurge: Determined by ST7800A Purge Timer Card

  • PostPurge: 15 sec

  • Early Spark Termination: Yes, 5 sec

  • Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card.

  • AirFlow Check: User selectable:

  • Second Stage Pilot Valve: Interrupted

  • Pilot Type: interrupted

  • Vibration: 0.5 G environment

  • Shipping Weight: 2.4 Kg

Reward Points

791 points will be rewarded to you when you buy this item.

Related Items

Recently Viewed Items

The cookie settings on this website are set to 'allow all cookies' to give you the very best experience. Please click Accept Cookies to continue to use the site.

Logo