Estimated Lead Time : Usually ships in 1 - 10 working days.
Manufacturer : Mitsubishi Electric
Q25HCPU
control method : Stored program iteration operation
Input / output control method : Refresh method (Direct access input / output possible by specifying direct access input / output (DX, DY))
Programming language Sequence control language : Relay symbol word, logic symbolic word, MELSAP 3 (SFC), MELSAP-L, function block, structured text (ST)
processing speed Sequence instructions LD X 0 : 34 ns
MOV D 0 D 1 : 102 ns
Constant scan : 0.5 - 2000 ms (Can be set in 0.5 ms increments)
Program capacity : 252 K steps (1008 Kbytes)
Memory capacity Program memory (drive 0) : 1008 KB
Memory card (RAM) (Drive 1) : The installed memory card capacity (maximum 2 Mbytes)
Memory card (ROM) (Drive 2) : (Flash card: up to 4 Mbytes, ATA card: up to 32 Mbytes)
Standard RAM (Drive 3) : 256 KB
Standard ROM (Drive 4) : 1008 KB
CPU shared memory QCPU standard area : 8 KB
Maximum number of stored files Program memory : 252 books
Memory card (RAM) : 287 (when using Q2MEM-2 MBS)
Memory card (ROM) Flash card : 288 books
ATA card : 512 pieces
Standard RAM : 3
Standard ROM : 252 books
Intelligent functional unit Parameter Maximum setting number Initial setting : 512 pieces
refresh : 256 pieces
Number of input / output devices : 8192 points (X / Y 0 to 1 FFF)
Number of input / output points : 4096 points (X / Y 0 to FFF)
Number of device points Internal relay [M] : Default 8192 points (M0 to 8191) (changeable)
Latch relay [L] : Default 8192 points (L0 to 8191) (changeable)
Link relay [B] : Default 8192 points (B 0 to 1 FFF) (changeable)
Timer [T] : Default 2048 points (T0 to 2047) (Shared by low-speed timer / high-speed timer) (Changeable) Low-speed timer / high- speed timer specified by instruction Low-speed timer / high-speed timer measurement unit is set by parameter (low-speed timer: 1 to 1000 ms, 1 ms increment, default 100 ms) (High-speed timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)
Integration timer [ST] : Default 0 point (Shared with low speed integration timer / high speed integration timer) (Changeable) Low speed integration timer / high speed integration timer specified by instruction Set the measurement unit of low speed integration timer / high speed integration timer by parameter (low speed integration timer: 1000 ms, 1 ms increment, default 100 ms) (High-speed integration timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)
Counter [C] : Normal counter: default 1024 points (C0 to 1023) (changeable) Interrupt counter: maximum 256 points (default 0 point, set by parameter)
Data register [D] : Default 12288 points (D 0 to 12287) (changeable)
Link register [W] : Default 8192 points (W 0 to 1 FFF) (changeable)
Annunciator [F] : Default 2048 points (F 0 to 2047) (changeable)
Edge relay [V] : Default 2048 points (V 0 to 2047) (changeable)
File register [R] Standard RAM : 32768 points (R 0 to 32767) Up to 13,1072 points can be used by block switching
SRAM card (1 Mbyte) : 32768 points (R 0 ~ 32767) Maximum 517120 points can be used by block switching
SRAM card (2 Mbytes) : 32768 points (R 0 to 32767) Maximum 1041408 points can be used by block switching
Flash card (2 Mbytes) : 32768 points (R 0 to 32767) Maximum 1041408 points can be used by block switching
Flash card (4 Mbytes) : 32768 points (R 0 ~ 32767) Up to 1042432 points can be used by block changeover
File register [ZR] Standard RAM : 131072 points (ZR 0 to 131071) Block switching not required
SRAM card (1 Mbyte) : 517120 points (ZR 0 to 517119) No block switching required
SRAM card (2 Mbytes) : 1041408 points (ZR 0 to 1041407) No block switching required
Flash card (2 Mbytes) : 1041408 points (ZR 0 to 1041407) No block switching required
Flash card (4 Mbytes) : 1042432 points (ZR 0 to 1042431) Block switching not required
Link special relay [SB] : 2048 points (SB 0 - 7 FF) (Device number is fixed)
Link special register [SW] : 2048 points (SW 0 to 7 FF) (Device number is fixed)
Step relay [S] : 8192 points (S 0 to 8191) (the number of device points is fixed)
Index register [Z] : 16 points (Z 0 ~ 15) (Device number is fixed)
Pointer [P] : 4096 points (P 0 ~ 4095) (Number of device points fixed) Use range of local pointer / common pointer can be set by parameter
Interrupt pointer [I] : 256 points (I 0 to 255) (the number of device points is fixed) Periodic interval of system interrupt pointer I 28 to 31 can be set by parameter (0.5 to 1000.0 ms, 0.5 ms increments) Default I 28: 100 ms, I 29: 40 ms, I 30: 20 ms , I31: 10 ms
Special relay [SM] : 2048 points (SM 0 to 2047) (Device number is fixed)
Special register [SD] : 2048 points (SD 0 to 2047) (the number of device points is fixed)
Function input [FX] : 16 points (FX 0 to F) (Device number is fixed)
Function output [FY] : 16 points (FY 0 to F) (the number of device points is fixed)
Function register [FD] : 5 points (FD 0 ~ 4) (Device number is fixed)
Link direct device : J□□ \ X□□, J□□ \ Y□□, J□□ \ SB□□, J□□ \ SB□□, J□□ \ SB□□, J□□ \ SW□□, J□□ \ SW□ Device specification form for directly accessing the link device of the network unit□
Intelligent functional unit device : Device specification that directly accesses buffer memory of intelligent function module Format: U□□ \ G□□
Latch (power outage hold) range : L 0 to 8191 (default 8192 points) [latch range can be set for B, F, V, T, ST, C, D, W]
RUN / PAUSE contact : One point of each RUN / PAUSE contact can be set from X 0 to 1 FFF
Clock function : Year, month, day, hour, minute, second, day of the week (leap year automatic discrimination) accuracy: -3.18 ~ + 5.25s (. TYP + 2.12s) / d at 0 °C accuracy: -3.93 ~ + 5.25s (TYP + . 1.90 s) / d at 25 ° C. Accuracy: -14.69 to +3.53 s (TYP. -3.67 s) / d at 55 ° C.
Allowable momentary power failure time : Depends on power supply unit
DC 5 V Internal current consumption : 0.64 A
External dimensions Height (H) : 98 mm
Width (W) : 27.4 mm
Depth (D) : 89.3 mm
mass : 0.20 Kg
Operating ambient temperature : 0 to 55 ° C
Storage ambient temperature : -25 to 75 ° C (-20 to 75 ° C when system includes AnS / A series unit)
Ambient operating humidity : 5 to 95% RH, non condensing (10 to 90% RH when the system includes AnS / A series unit)
Storage ambient humidity : 5 to 95% RH, non condensing (10 to 90% RH when the system includes AnS / A series unit)
Anti-vibration Meets JIS B 3502, IEC 61131-2 When there is intermittent vibration : Frequency: 5 to 8.4 Hz, One amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m / s 2 Sweep count: 10 times in X, Y, Z directions
When there is continuous vibration : Frequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2
Impact resistance : Meets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)
Use atmosphere : No corrosive gas
Use elevation : 0 to 2000 m
Installation location : In the control panel
Over voltage category : II or less
Pollution degree : 2 or less
Device class : Class I
Shipping Weight : 1.2 Kg