Basic model QCPU Q00JCPU

Basic model QCPU Q00JCPU

Your Price: $290.00
Estimated Lead Time : In stock. Usually ships in 3-5 working days.
Part Number:Q00JCPU

Condition : Brand New

Warranty : 12 months 

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

  • Estimated Lead Time : In stock. Usually ships in 3-5 working days.

  • Manufacturer : Mitsubishi Electric

  • Q00JCPU

  • Basic model QCPU Q00JCPU

  • control method : Stored program iteration operation

  • Input / output control method : Refresh method (Direct access input / output possible by specifying direct access input / output (DX, DY))

  • Programming language Sequence control language : Relay symbol word, logic symbolic word, MELSAP 3 (SFC), MELSAP-L, function block, structured text (ST)

  • processing speed Sequence instructions LD X 0 : 200 ns

  • MOV D 0 D 1 : 700 ns

  • Constant scan : 1 ~ 2000 ms (Can be set in 1 ms increments)

  • Program capacity : 8K steps (32K bytes)

  • Memory capacity Program memory (drive 0) : 58 KB

  • Standard ROM (Drive 4) : 58 KB

  • Maximum number of stored files Program memory : 6

  • Standard ROM : 6

  • Intelligent functional unit Parameter Maximum setting number Initial setting : 512 pieces

  • refresh : 256 pieces

  • Number of input / output devices : 2048 points (X / Y 0 to 7 FF)

  • Number of input / output points : 256 points (X / Y 0 to FF)

  • Number of device points Internal relay [M] : Default 8192 points (M0 to 8191) (changeable)

  • Latch relay [L] : Default 2048 points (L0 to 2047) (changeable)

  • Link relay [B] : Default 2048 points (B 0 - 7 FF) (changeable)

  • Timer [T] : Default 512 points (T0 to 511) (Shared with low-speed timer / high-speed timer) (Changeable) Low-speed timer / high- speed timer specified by instruction Low-speed timer / high-speed timer measurement unit is set by parameter (low-speed timer: 1 to 1000 ms, 1 ms increment, default 100 ms) (High-speed timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)

  • Integration timer [ST] : Default 0 point (Shared with low speed integration timer / high speed integration timer) (Changeable) Low speed integration timer / high speed integration timer specified by instruction Set the measurement unit of low speed integration timer / high speed integration timer by parameter (low speed integration timer: 1000 ms, 1 ms increment, default 100 ms) (High-speed integration timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)

  • Counter [C] : Normal counter: default 512 points (C 0 to 511) (changeable) Interrupt counter: maximum 128 points (default 0 point, set by parameter)

  • Data register [D] : Default 11136 points (D0 to 11135) (changeable)

  • Link register [W] : Default 2048 points (W 0 to 7 FF) (changeable)

  • Annunciator [F] : Default 1024 points (F0 to 1023) (changeable)

  • Edge relay [V] : Default 1024 points (V 0 to 1023) (changeable)

  • Link special relay [SB] : 1024 points (SB 0 to 3 FF) (Device number is fixed)

  • Link special register [SW] : 1024 points (SW 0 to 3 FF) (the number of device points is fixed)

  • Step relay [S] : 2048 points (S 0 ~ 127 / block) (Device number is fixed)

  • Index register [Z] : 10 points (Z 0 ~ 9) (Device number is fixed)

  • Pointer [P] : 300 points (P 0 ~ 299) (Device number is fixed)

  • Interrupt pointer [I] : 128 points (I 0 to 127) ( Number of device points is fixed) Periodic interval of system interrupt pointer I 28 to 31 can be set by parameter. (2 to 1000 ms, 1 ms increments) Default I 28: 100 ms, I 29: 40 ms, I 30: 20 ms, I 31 : 10 ms

  • Special relay [SM] : 1024 points (SM 0 ~ 1023) (Device number is fixed)

  • Special register [SD] : 1024 points (SD 0 ~ 1023) (Device number is fixed)

  • Function input [FX] : 16 points (FX 0 to F) (Device number is fixed)

  • Function output [FY] : 16 points (FY 0 to F) (the number of device points is fixed)

  • Function register [FD] : 5 points (FD 0 ~ 4) (Device number is fixed)

  • Link direct device : J□□ \ X□□, J□□ \ Y□□, J□□ \ SB□□, J□□ \ SB□□, J□□ \ SB□□, J□□ \ SW□□, J□□ \ SW□ Device specification form for directly accessing the link device of the network unit□

  • Intelligent functional unit device : Device specification that directly accesses buffer memory of intelligent function module Format: U□□ \ G□□

  • Latch (power outage hold) range : L 0 to 2047 (default 2048 points) [latch range can be set for B, F, V, T, ST, C, D, W]

  • RUN / PAUSE contact : One point of each RUN / PAUSE contact can be set from X 0 to 7 FF

  • Clock function : Year, month, day, hour, minute, second, day of the week (leap year automatic discrimination) accuracy: -3.20 ~ + 5.27s (. TYP + 1.98s) / d at 0 °C accuracy: -2.57 ~ + 5.27s (TYP + . 2.22 s) / d at 25 ° C. Accuracy: -11.68 to +3.65 s (TYP. -2.64 s) / d at 55 ° C.

  • Allowable momentary power failure time : Within 20 ms (AC 100 V or more)

  • DC 5 V Internal current consumption : 0.26 A

  • External dimensions Height (H) : 98 mm

  • Width (W) : 244.4 mm

  • Depth (D) : 98 mm

  • mass : 0.66 Kg

  • Power supply part :

  • Input supply voltage : AC 100 to 240 V (-15% to + 10%)

  • Input frequency : 50/60 Hz ± 5%

  • Input voltage distortion ratio : Within 5%

  • Input maximum apparent power : 105VA

  • Inrush current : 40 A within 8 ms

  • Rated output current DC 5V : 3A

  • Overcurrent protection DC 5V : 3.3 A or more

  • Overvoltage protection DC 5V : 5.5 to 6.5 V

  • efficiency : 65% or more

  • Withstand voltage : Input . LG collective and output . FG all at once AC 2300 V / 1 min (altitude 0 to 2000 m)

  • Insulation resistance : Input . LG collective and output . Between FG batch, input batch and LG, batch output and FG: 500 MV DC insulation resistance meter 10 MΩ or more

  • Operation indication : LED display (normal: green lighting, abnormal: off, CPU part "POWER" LED)

  • fuse : Built-in (user replaceable)

  • Contact output unit : None

  • External wiring connection method : Screw terminal block (M3.5 screw)

  • Base part :

  • Number of input / output units : Five

  • Applicable unit : MELSEC-Q series unit

  • Operating ambient temperature : 0 to 55 ° C

  • Storage ambient temperature : -25 to 75 ° C

  • Ambient operating humidity : 5 to 95% RH, non condensing

  • Storage ambient humidity : 5 to 95% RH, non condensing

  • Anti-vibration Meets JIS B 3502, IEC 61131-2 When there is intermittent vibration : Frequency: 5 to 8.4 Hz, One amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m / s 2 Sweep count: 10 times in X, Y, Z directions

  • When there is continuous vibration : Frequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2

  • Impact resistance : Meets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)

  • Use atmosphere : No corrosive gas

  • Use elevation : 0 to 2000 m

  • Installation location : In the control panel

  • Over voltage category : II or less

  • Pollution degree : 2 or less

  • Device class : Class I

  • Shipping Weight : 1.7 Kg

Reward Points