Temperature Converter with Trip Values KFD2-GUT-1.D
Temperature Converter with Trip Values KFD2-GUT-1.D

Temperature Converter with Trip Values KFD2-GUT-1.D

0 Review(s)
USD699.00
Retail Price:USD804.00
Your Savings:USD105.00(13%)
Availability: Estimated Lead Time : 8 Weeks
Part Number: KFD2-GUT-1.D
Manufacturer:Pepperl+Fuchs
Condition : Brand New
Warranty : 12 months 
Write a Review

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com.All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

NII REF No : IAFD111611121121

  • Estimated Lead Time : 8 Weeks

  • Manufacturer : Pepperl+Fuchs

  • Temperature Converter with Trip Values KFD2-GUT-1.D

  • 1-channel signal conditioner

  • 24 V DC supply (Power Rail)

  • Thermocouple, RTD, potentiometer or voltage input

  • Redundant TC input

  • Current output 0/4 mA ... 20 mA

  • 2 relay contact outputs

  • Configurable by PACTware or keypad

  • Line fault (LFD) and sensor burnout detection

  • Up to SIL 2 acc. to IEC 61508/IEC 61511

  • Signal type : Analog input

  • Connection : terminals 23+, 24- or power feed module/Power Rail

  • Rated voltage : 20 ... 30 V DC

  • Rated current : approx. 100 mA

  • Power dissipation/power consumption : ≤2 W / 2.2 W

  • Connection : terminals 1, 2, 3, 4, 6 

  • RTD : Pt100, Pt500, Pt1000, Ni100, Ni1000

  • Measuring current : approx. 400 µA

  • Types of measuring : 2-, 3-, 4-wire technology

  • Lead resistance : max. 50Ω

  • Measuring circuit monitoring : sensor breakage, sensor short-circuit

  • Thermocouples : type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)

  • Cold junction compensation : external and internal

  • Measuring circuit monitoring : sensor breakage

  • Potentiometer : 0.8 ... 20 k?

  • Types of measuring : 2-, 3-, 5-wire technology

  • Voltage : 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV

  • Input resistance : ≥ 250 k? (0 ... 10 V) 
    min. 1 M? (0 ... 1 V, -100 ... 100 mV)

  • Connection : output I: terminals 10, 11, 12 
    output II: terminals 16, 17, 18 
    output III: terminals 8+, 7-

  • Output I, II : relay

  • Contact loading : 250 V AC / 2 A / cos ? ≥ 0.7 ; 40 DC / 2 A

  • Mechanical life : 5 x 107 switching cycles

  • Energized/De-energized delay : approx. 20 ms / approx. 20 ms

  • Output III : Analog current output

  • Current range : 0 ... 20 mA or 4 ... 20 mA

  • Open loop voltage : max. 24 V DC

  • Load : max. 650 Ω

  • Fault signal : downscale I ≤3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)

  • Collective error message : Power Rail

  • Transfer characteristics-Sampling rate : approx. 700 ms

  • Electromagnetic compatibility

  • Directive 2014/30/EU : EN 61326-1:2013 (industrial locations)

  • Low voltage

  • Directive 2014/35/EU : EN 61010-1:2010

  • Electromagnetic compatibility : NE 21:2007

  • Degree of protection : IEC 60529:2001

  • Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)

  • Degree of protection : IP20

  • Mass : 300 g

  • Dimensions : 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3

  • Mounting : on 35 mm DIN mounting rail acc. to EN 60715:2001

  • Shipping Weight : 1 Kg

Reward Points

699 points will be rewarded to you when you buy this item.

Related Items

Recently Viewed Items

The cookie settings on this website are set to 'allow all cookies' to give you the very best experience. Please click Accept Cookies to continue to use the site.