This product has been replaced with:
NEW REPLACEMENT
KFD2-GUT-EX1.D : Temperature Converter with Trip Relays
Manufacturer : Pepperl+Fuchs
Product No. : KFD2-GU-Ex1
Product type : Temperature Trip Amplifier
-
General specifications
-
Signal type : Analog input
-
Supply
-
Connection : Power Rail or terminals 14+, 15-
-
Rated voltage : 19 ... 35 V DC
-
Ripple : within the supply tolerance
-
Power dissipation : 0.8 W
-
Power consumption : 0.8 W
-
Interface
-
Programming interface : programming socket
-
Input
-
Connection side : field side
-
Connection : terminals 1, 2, 3, 4, 5, 6
-
Thermocouples : type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985)
-
Voltage : 0 ... 10 V , 2 ... 10 V
-
Current : 0 ... 20 mA , 4 ... 20 mA
-
Load : 20 O for 20 mA; 200 kO for 10 V
-
Output
-
Connection side : control side
-
Connection : output I: terminals 7, 8, 9; output II: terminals 10, 11, 12
-
Output I, II : relay
-
Contact loading : 253 V AC/2 A/500 VA/cos f min. 0.7; 40 V DC/2 A resistive load
-
Mechanical life : 2 x 107 switching cycles
-
Transfer characteristics
-
Resolution : temperature: 0.0625 °C, resistance: 62.5 mO, voltage: 62.5 µV, current: 625 nA
-
Influence of supply voltage : < 0.001 % of sensor input range
-
Input delay : = 370 ms (rise time and energizing delay of relay)
-
Indicators/settings
-
Display elements : LEDs
-
Configuration : via PACTware
-
Labeling : space for labeling at the front
-
Directive conformity
-
Electromagnetic compatibility
-
Directive 2014/30/EU : EN 61326-1:2013 (industrial locations)
-
Low voltage
-
Directive 2014/35/EU : EN 61010-1:2010
-
Conformity
-
Electromagnetic compatibility : NE 21:2006
-
Degree of protection : IEC 60529:2001
-
Ambient conditions
-
Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)
-
Mechanical specifications
-
Degree of protection : IP20
-
Connection : screw terminals
-
Mass : approx. 150 g
-
Dimensions : 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
-
Mounting : on 35 mm DIN mounting rail acc. to EN 60715:2001
-
Data for application in connection with hazardous areas
-
EU-Type Examination Certificate : BAS 98 ATEX 7152
-
Marking :II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C = Tamb = 60 °C) , [circuit(s) in zone 0/1/2]
-
Certificate : TÜV 99 ATEX 1493 X
-
Marking : II 3G Ex nA nC IIC T4
-
Directive conformity
-
Directive 2014/34/EU : EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
-
International approvals
-
UL approval
-
Control drawing : 116-0173 (cULus)
-
IECEx approval : IECEx BAS 06.0022
-
Approved for : [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
-
Shipping Weight : 3 Kg