6% off
Pressure Transmitter IPX2/4-20MA/3-20PSIG/25-40PSIG/-EEP-FR1(EXIMP)
Pressure Transmitter IPX2/4-20MA/3-20PSIG/25-40PSIG/-EEP-FR1(EXIMP)

Pressure Transmitter IPX2/4-20MA/3-20PSIG/25-40PSIG/-EEP-FR1(EXIMP)

0
0
5
USD1,137.00
USD1,207.00
USD70.00(6%)
Estimated Lead Time : 4 Weeks
IPX2/4-20MA/3-20PSIG/25-40PSIG/-EEP-FR1(EXIMP)
Moore Industries
  • Estimated Lead Time: 4 Weeks

  • Manufacturer: Moore Industries

  • Pressure Transmitter IPX2/4-20MA/3-20PSIG/25-40PSIG/-EEP-FR1(EXIMP)

  • Moore explosion proof current to pressure transmitter

  • Accuracy: <±0.25% of span including the combined effect of linearity, hysteresis and repeatability (between 0 and 3psig output, error will not exceed ±1.0% of span)

  • Stability: Not to degrade from stated accuracy for six months

  • Step Response: <0.2 seconds into 100ml load (6 in3) from 10% to 90% ofspan; Not guaranteed below 3psig output

  • Supply Pressure Effect: Negligible from 20-40psig,steady pressure

  • Air Capacity:5.0SCFM minimum (20psig supply, 0psig output)

  • Relief Capacity: 2.5SCFM minimum (15psig output)

  • Air Supply: Instrument air only, 20-40psig.

  • Gas Supply with -NG1 or-NG2 Option: 17-40psig.Same cleanliness as instrument air. H2 S not to exceed 20ppm

  • Maximum Input: 80psig without damage for units with output pressure rating of >15psig; 45psig without damage for units with output press 15psig

  • Voltage Drop: 5V, maximum

  • Weight IPX2: 2.4kg (5.3 lbs)

  • Air Consumption (Dead-ended): At 3-15psig output 20psig supply, average steady state consumption* of 4.7SCFH (min [email protected] 3psig, max [email protected]);
    40psig supply, max 9SCFH @15psig output;40psig supply, max 10SCFH @30psig output

  • Natural Gas Consumption (Dead-ended): At 3-15psig output 20psig supply, average steady state consumption* of 5.7SCFH,(min [email protected] 3psig, max [email protected]);17psig supply, max 5.9SCFH @15psig output; 40psig supply, max 12SCFH @30psig output;

  • Mounting Position Effect:Negligible, unit can be mounted in any position; refer to user manual for special conditions of use with natural gas supply or outdoor environments.

  • Operating & Storage Range:-40°C to +85°C(-40°F to +185°F)

  • Ambient Temperature Effect: <±0.025% ofspan/°C, maximum from-20°C to 80°C;<±0.1% of span/°C,maximum

  • RFI/EMI Effect:<±0.25% of span change at in fi eld strengths of 10V/[email protected] frequencies of 20-1000MHz

  • Vibration Effect: Meets ANSI/ISA-75 13.01-1996 (R2007) 5.3.5 as follows: 5-15Hz, 2mm peak-to-peak;15-150Hz, 1g;150-2000Hz, 0.5g

  • Relative Humidity: 0-100%, non-condensing

  • Zero & Span: Screw adjusts zero or span by ±10% minimum, non-interactive

  • Shipping Weight : 3.4 Kg

[short_review]
[long_review]
Did you find this helpful?  [rev_helpful] of [rev_votes] Found Helpful
Reviewed by: (Verified Buyer)  from [user_city]. [user_email] on [review_date]
[rating]
There are no reviews for this product!

Reward Points

1137 points will be rewarded to you when you buy this item.

Related Items

https://www.nexinstrument.com/assets/images/IPX2_thumbnail.png

Feature 5

price*1.3 (Change QTE)

Recently Viewed Items

Legal Disclaimer

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.