CJ1W-DA08C Analog Output Unit

CJ1W-DA08C Analog Output Unit

Your Price: $558.00
Retail Price:$641.00
Your Savings:$83.00(13%)
Estimated Lead Time : In stock. Usually ships in 7-10 working days.
Part Number:CJ1W-DA08C

Condition : Brand New

Warranty : 12 months 

You need to be a registered customer to order this product. Please Login to your account or click here to Register.

Sign in with Facebook

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

  • Even though we have this part in stock, it may take several days for internal process to complete. Goods will be delivered within 5 -7 working days.

  • CJ1W-DA08C

  • Unit type : CJ-series Special I/O Unit

  • Isolation *1 : Between I/O and Controller signals: Photocoupler (No isolation between I/O signals.)

  • External terminals : 18-point detachable terminal block (M3 screws)

  • Power consumption: 5 VDC, 140 mA max.

  • External power supply *2: 24 VDC (inrush current: 20 A max., pulse width: 1 ms min.)

  • External power supply *2 : 170 mA max.

  • Dimensions (mm): 31 × 90 × 65 mm (W × H × D)

  • Weight: 150 g max.

  • General specifications Conforms to general specifications for CJ-series Series

  • Output specifications Number of analog outputs: 8

  • Output signal range *3: 4 to 20 mA

  • Maximum permissible load resistance: 350 O

  • Resolution : 4,000/8,000 *8

  • Set data : 16-bit binary data

  • Accuracy*4 25°C: ±0.3% of F.S.

  • Accuracy*4 0°C to 55°C :±0.6% of F.S.

  • D/A conversion period *5: 1.0 ms or 250 µs per point *8

  • Output functions

  • Output hold function:

  • Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.

  • When the Conversion Enable Bit is OFF. *6

  • In adjustment mode, when a value other than the output number is output during adjustment. *7

  • When output setting value error occurs or Controller operation stops.

  • When the Load is OFF.

  • Scaling : Supported only for a conversion period of

  • 1 ms and resolution of 4,000.

  • Setting values in any specified unit within a

  • range of ±32,000 as the upper and lower limits allows D/A conversion to be executed and analog signals to be output with these values as full scale.

  • Output functions Offset/gain adjustment: Supported

  • Shipping Weight: 1.2 Kg