CJ1W-AD042 | Omron |Analog Input Unit
CJ1W-AD042 | Omron |Analog Input Unit

CJ1W-AD042 | Omron |Analog Input Unit

0 Review(s)
USD1,228.00
Retail Price:USD1,412.00
Your Savings:USD184.00(13%)
Availability: Estimated Lead Time : Usually ships in 1-10 working days.
Part Number: CJ1W-AD042
Manufacturer:Omron
Condition : Brand New
Warranty : 12 months 
Write a Review

NII REF No : IAAH111711081122

NEX Instrument Inc is not an authorized dealer, agent or associate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.nexinstrument.com.All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the right of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All items are 100% authentic and legally purchased from authorized sources.

  • Usually ships in 1 - 10 working days.

  • CJ1W-AD042

  • Analog Input Units CJ1W-AD042

  • Unit type: CJ-series Special I/O Unit

  • Isolation *1: Between I/O and Controller signals: Digital isolator (No isolation between I/O signals.)

  • External terminals: 18-point detachable terminal block (M3 screws)

  • Power consumption: 520 mA max. at 5 VDC

  • Dimensions (mm): 31 × 90 × 65 mm (W × H × D)

  • Weight: 150 g max.

  • General specifications: Conforms to general specifications for CJ Series.

  • Input specifications

  • Number of analog inputs: 4

  • Input signal range *2: 1 to 5 V, 0 to 10 V, - 5 to 5 V, - 10 to 10 V, 4 to 20 mA, *4

  • Maximum rated input

  • (for 1 point) *5: Voltage Input: ± 15 V, Current Input: ± 30 mA

  • Input impedance: Voltage Input: 1 MO min. Current Input: 250 O (rated value)

  • Converted output data: 16-bit binary data

  • Accuracy *7: 25 °C *8: Voltage Input: ± 0.2% of F.S. Current Input: ± 0.4% of F.S.

  • 0 °C to 55 °C: Voltage Input: ± 0.4% of F.S. Current Input: ± 0.6% of F.S.

  • A/D conversion period *9 : 20 µs/1 point, 25 µs/2 points, 30 µs/3 points, 35 µs/4 points

  • Input functions

  • Mean value processing: Stores the last "n" data conversions in the buffer, and stores the mean value of the conversion values. Buffer number: n = 2, 4, 8, 16, 32,

  • 64, 128, 256, 512

  • Peak value holding: Stores the maximum conversion value while the Peak Value Hold Bit is ON.

  • Scaling : Setting values in any specified unit within a range of ±32,000 as the upper and lower limits allows A/D conversion to be executed and analog signals to

  • be output with these values as full scale.

  • Input disconnection detection: Detects the disconnection and turns ON the Disconnection Detection Flag. *10

  • Direct conversion : A/D conversion is performed and the converted value is refreshed when the ANALOG INPUT

  • DIRECT CONVERSION instruction (AIDC) is executed.

  • This instruction is supported by the CJ2H-CPU[][](-EIP) CPU Units with unit version 1.1 or later, and CJ2M-CPU[][].

  • CJ1, NJ501, and CP1H CPU Units and NSJ Controllers do not support direct conversion

  • Shipping Weight : 2 Kg

Reward Points

1228 points will be rewarded to you when you buy this item.

Related Items

Recently Viewed Items

The cookie settings on this website are set to 'allow all cookies' to give you the very best experience. Please click Accept Cookies to continue to use the site.