Estimated Lead Time : Usually ships in 1 - 10 working days.
Manufacturer : Mitsubishi Electric
AJ65SBTB2N-16R
CC-Link small type remote I / O unit (contact output, terminal block) AJ65SBTB2N-16R
Number of output points : 16 points
Rated switching voltage / current : DC 24 V 2A (resistance load) / 1 point, AC 240 V 2 A (cos φ = 1) / 1 point, 8 A / 1 common
Minimum opening / closing load : DC 5 V 1 mA
Maximum switching voltage : AC 264 V DC 125 V
lifespan mechanical : Over 20 million times
Electrical : Rated switching voltage . current load: 100,000 times or more AC 200 V 1.5 A, AC 240 V 1A (COS φ = 0.7): 100 thousand times or more AC 200 V 1A, AC 240 V 0.5 A (COS φ = 0.35): 100,000 times or more DC 24 V 1A, DC 100 V 0.1 A L / R = 7 ms): 100 thousand times or more
Maximum switching frequency : 3600 times / hour
Output response time OFF → ON : 10 ms or less
ON → OFF : 12 ms or less
Output common method : 16 points 1 common (terminal trapezoid 2 wire type)
Output isolation method : Relay insulation
Withstand voltage : Between AC external terminal and ground: AC 2830 Vrms / 3 cycles (altitude 2000 m) Between DC external terminals and ground: AC 500 V 1 min
Insulation resistance : AC external terminal all together and ground, DC external terminal collective to ground: 500 MV DC insulation resistance meter 10 MΩ or more
Station type : Remote I / O station
Number of occupied stations : 1 station
Unit power supply Voltage : DC 20.4 to 26.4 V (ripple ratio within 5%)
Current : 120 mA or less (24 VDC, all points ON)
External wiring connection method : Communication part, unit power supply part: 7 points 2 piece terminal block (M3 screw) I / O power supply part, input / output part: 34 points Direct mounting terminal block (M3 screw)
External dimensions Height (H) : 50 mm
Width (W) : 179 mm
Depth (D) : 40 mm
mass : 0.35 Kg
Operating ambient temperature : 0 to 55 ° C
Storage ambient temperature : -20 to 75 ° C
Ambient operating humidity : 10 to 90% RH, non condensing
Storage ambient humidity : 10 to 90% RH, non condensing
Anti-vibration Meets JIS B 3502, IEC 61131-2 When there is intermittent vibration : Frequency: 5 to 8.4 Hz, One amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m / s 2 Sweep count: 10 times in X, Y, Z directions
When there is continuous vibration : Frequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2
Impact resistance : Meets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)
Use atmosphere : No corrosive gas
Use elevation : 0 to 2000 m
Installation location : In the control panel
Over voltage category : II or less
Pollution degree : 2 or less
Shipping Weight : 2 Kg